The chart below lists the minimum efficiency standards for commercial furnaces and boilers taken from ANSI/ASRAE/IESNA Standard 90.1 – 2004, Table 6.8.1.E. It illustrates the type of information available in this standard which also covers minimum efficiency standards for air conditioning and condensing units, electrically operated and applied heat pumps, water chilling packages, packaged systems, and other systems. (The reader should reference the 90.1 standard directly to see all conditions associated with information listed in the table.) Efficiency (E) is defined as thermal efficiency.

Equipment Type

Size Category (Input)

Minimum Efficiency

Test Procedure

Warm Air Furnace, Gas-Fired

≥225,000 Btu/h

80% E at max. capacity

ANSI Z21.47

Warm Air Furnace, Oil-Fired

≥225,000 Btu/h

81% E at max. capacity

UL 727

Duct Furnaces, Gas-Fired

All

80% E at max. capacity

ANSI Z83.9

Unit Heaters, Gas-Fired

All

80% E at max. capacity

ANSI Z83.8

Unit Heaters, Oil-Fired

All

80% E at max. capacity

UL 731

Boilers, Gas-Fired

≥2,500,000 Btu/h

80% E at max. capacity

H.I. Htg. Boiler Standard

Boilers, Oil-Fired

≥2,500,000 Btu/h

83% E at max. capacity

H.I. Htg. Boiler Standard